Product Data Sheet
A Regal Brand
www.marathonsp.com 1
133X596
Replace “x” with 1, 2, or 3 for number of poles
Add sufx “CH” for snap-on hinged cover
Power Terminal Block
510 Amps 600 Volts AC/DC
Wire Range
• Line: (2) 250kcmil - 1/0
• Load: (12) #4 - 14 AWG
Electrical Ratings
• 510 Amps
• 600V per UL 1059 & CSA 22.2 No.158, class B & C requirements
• Short circuit current ratings (SCCR): See SCCR section below for specications.
• CU7AL - 75°C connector terminal rating with copper or aluminum wire
• Factory & Field Wiring
Agency Compliance
• UR - UL Recognized Terminal Block, Evaluated to UL 1059, File No.XCFR2.E62806
• CSA - certifed to C22.2 No. 158, File No. LR19766 (wire classes B & C only)
• CE compliant to IEC 60947-7-1
Material Information
• Insulator base:
• Thermoplastic
• Flammability rating of insulator base UL94V0
• Insulator base temperature rating: -40°C to 125°C (UL RTI)
• Connector: aluminum, tin plated
• Line terminal screws: steel, nickel plated
• Load terminal screws: aluminum, tin plated
• Connector mounting screws: steel, zinc plated
• RoHS compliant
www.marathonsp.com 2
Termination Specications
Line Side Wire Size
(CU Stranded) Torque Wires /
Terminal Wire Class (UL) 1
250 kcmil 31.1 N·m (275 lbf·in) 1 B, C
4/0 31.1 N·m (275 lbf·in) 1 B, C, G, H
3/0 - 1/0 31.1 N·m (275 lbf·in) 1 B, C, G, H, I (DLO)
• Aluminum stranded wire range: 250 kcmil - 1/0
• Wire strip length: 1 9/16in. (40mm)
• Terminal screw drive: 5/16 in. hex
PDS 0038 REV-E 10/16/13
• Solid copper wire range: #10 - 14 AWG
• Aluminum stranded wire range: 4 - 14 AWG
• Wire strip length:
• top row: 1/2 in. (13mm)
• middle row: 11/16 in. (18mm)
• bottom row: 15/16 in. (24mm)
Load Side Wire Size
(CU Stranded) Torque Wires /
Terminal Wire Class (UL) 1
4 AWG 4 N·m (35 lbf·in) 1 B, C
6 - 8 4 N·m (35 lbf·in) 1 B, C, G, H, I (DLO)
10 4 N·m (35 lbf·in) 1-2 B, C, I (DLO)
12 - 14 4 N·m (35 lbf·in) 1-4 B, C
1-2 I (DLO)
1 For information on copper stranded wire classes please reference:
http://www.marathonsp.com/CatalogPDFs/Flexible-Stranded-Wire.pdf
www.marathonsp.com 3
Short Circuit Current Ratings (SCCR)
• The suitable conductor ranges are limited to the table values only for achieving the SCCR in excess of the
default rating of 10,000A.
• Other conductor combinations within the “Terminal Specications” noted are suitable for achieving a
SCCR of 10,000A (the default rating of terminal blocks).
• Enclosure size – Investigated with a minimum 16x12x6 enclosure. Use in smaller enclosures is subject to
end use evaluation.
Wire
Classes
Suitable
Conductors
Max Overcurrent Protection Fuse Required
Amp Rating / Class SCCR RMS
Sym. Amps
600V. Max
Line Load J T RK1 RK5 G CC
B, C 250 - 1/0 4 - 10 450 450 400 100 60 30 100,000
G, H, I 3/0 - 1/0 6 - 14 150 150 100 30 60 30 100,000
(*) 250 - 1/0 4 - 14 None 10,000
SCCR With Fuses
Installation & Accessories
• Mounting (Panel):
• For use with #10 fastener.
• Torque mounting fastener to 25-30 lbf·in (2.8 - 3.4 N·m).
• Covers:
• Snap-on hinge covers available upon request
• Catalog Number: CH133x (replace “x” with number of poles)
• Covers are black thermoplastic
• Accessory covers are not intended to provide insulation for electrical spacings.
• Marker Strip: white vinyl strip with mounting screws available.
• Printing options available, consult customer service for specications.
PDS 0038 REV-E 10/16/13
* Any wire class evaluated (see terminal specication section)
www.marathonsp.com 4
Drawing
PDS 0038 REV-E 10/16/13