For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 43
Low Voltage Supplementary Fuses
Low Voltage
Supplementary
Fuses
For superior electrical protection, Cooper Bussmann recommends upgrading BAF,
BAN and KTK fuse applications to Low-Peak LP-CC fuses See page 19.
Recommended fuse blocks/fuse holders for 1332”x 1
12 fuses
• See page 40 Data Sheets: KTK-1011 KLM-2020
Data Sheet: 2046 (0-30)
Data Sheet: 2011 (0-30)
Specifications
Class: Supplemental
Description: Fast-acting
supplementary fuse.
Dimensions: 1332” x 1 12
(10.3 x 38.1mm).
Construction: Fibre
cartridge; nickel plated
brass endcaps.
Ratings:
Volts — 250Vac (210-15A)
— 125Vac (20-30A)
Amps — 1-6A
IR — 10,000A @ 125Vac (210-30A)
— 35A (210-1A @ 250Vac)
— 100A (112-6A @ 250Vac)
— 200A (614-10A @ 250Vac)
— 750A (12A- 15A @ 250Vac)
Agency Information: CE, Std. 248-14,
UL 0-15/250V, Guide JDYX, File E19180
CSA Certified, 0-15/250V, Class
1422-01, File 53787.
Features and Benefits
• Low cost supplemental protection of
125V and 250V non-inductive circuits.
• Upgrade with LP-CC product to reduce
SKU investment and minimize potential
arc-flash hazards. (and minimize
potential for misapplying fuse.)
Typical Applications
• General Purpose Circuits
• Lighting Circuit Protection
• Meter Circuits
Catalog Numbers (Amps)
BAF-210 BAF-2 BAF-8
BAF-14BAF-2 12BAF-9
BAF-12BAF-3 BAF-10
BAF-610 BAF-4 BAF-12
BAF-810 BAF-5 BAF-15
BAF-1 BAF-6 BAF-20
BAF-1 12BAF-6 14BAF-25
BAF-1 810 BAF-7 BAF-30
*All have interrupting rating of 10,000A at 125V.
Specifications
Class: Supplemental
Description: Fast-acting
supplementary fuse.
Dimensions: 1332” x 1 12
(10.3 x 38.1mm).
Construction: Fibre tube.
Ratings:
Volts — 250Vac
Amps — 1-30A
IR — 35A (1.1-3.5A)
— 100A (3.6-10A)
— 200A (10.1-15A)
— 750A (15.1-30A)
Features and Benefits
• Low cost supplemental protection of
125V and 250V non-inductive
circuits.
• Upgrade with LP-CC product to
reduce SKU investment and mini-
mize potential arc-flash hazards.
(and
minimize potential for misapplying
fuse.)
Typical Applications
• General Purpose Circuits
• Lighting Circuit Protection
• Meter Circuits
Catalog Numbers (Amps)
BAN-1 BAN-5 BAN-12 BAN-30
BAN-2 BAN-6 BAN-15
BAN-3 BAN-8 BAN-20
BAN-4 BAN-10 BAN-25
Recommended Fuse blocks 110 to 30A
Catalog Numbers
Terminal Type
Screw with Pressure Plate w/
Quick Connect Quick Connect Box Lug Poles
BM6031SQ BM6031PQ BM6031B 1
BM6032SQ BM6032PQ BM6032B 2
BM6033SQ BM6033PQ BM6033B 3
KTK & KLM
Specifications
Class: Supplemental
Description: Fast-
acting supplementary
fuse.
Dimensions: 1332” x
1 12(10.3 x 38.1mm).
Construction:
Melamine tube; nickel
plated brass endcaps.
Ratings:
Volts — KTK: 600Vac (or less)
— KLM: 500Vac/600Vdc (110A to 18A)
— 500Vac/dc (210-10A)
— 500Vac/600Vdc (12-30A)
Amps 110-30A
IR — KTK: 100,000A RMS Sym. (UL)
— KLM: 10,000A RMS Sym. (UL)
Agency Information: CE, Std. 248-14,
KTK-UL Listed, Guide JDYX, File E19180,
KLM-UL Recognized, Guide JFHR2, File
E56412, CSA Certified, File 53787, Class
1422-01, HRC-Misc.
Features and Benefits
• Low cost supplemental protection of 600V
or less non-inductive circuits.
• Upgrade with LP-CC product to reduce
SKU investment and minimize potential
arc-flash hazards.
Typical Applications
• Control Circuits
• Lighting Circuit Protection
• Meter Circuits
Catalog Numbers (Amps)
600Vac - UL Listed and CSA
KTK-
110 KTK-34KTK-4 KTK-12 KTK-50
KTK-18KTK-1 KTK-5 KTK-15
KTK-210 KTK-1 14KTK-6 KTK-20
KTK-14KTK-1 12KTK-7 KTK-25
KTK-310 KTK-2 KTK-7 12KTK-30
KTK-410 KTK-2 12KTK-8 KTK-35
KTK-12KTK-3 KTK-9 KTK-40
KTK-610 KTK-3 12KTK-10 KTK-45
*500Vac/dc - UL Recognized and CSA.
KLM-
110 KLM-34KLM-5 KLM-20
KLM-18KLM-1 KLM-6 KLM-25
KLM-210 KLM-1 12KLM-8 KLM-30
KLM-14KLM-2 KLM-10
KLM-310 KLM-3 KLM-12
KLM-12KLM-4 KLM-15
*KLM-(110-18A & 12-30A): 500Vac/600Vdc.
1332”x 1
12 Fast-acting fuses
BAF BAN