Environmental Specifications
Temperature ratings 0 to + 40°C operational without de-rating, up to 60°C with de-rating (see installation manual
for deratings)
Altitude ratings Up to 3,300 ft (1,000 meters) without de-rating, de-rate nominal current by 1% for each additional 330 ft
( 100m) up to 10,000 ft ( 3,000 m)
Limit to 6,600 ft (2,000 m) if supplied by corner grounded distribution system
Humidity Up to 95% non-condensing , IEC 60068-2-3
Vibration resistance 1.5 mm peak to peak from 3 to 13 Hz conforming to EN/IEC 600068-2-6, 1 gn from 13 to 200 Hz
conforming to IEC/EN 60068-2-8
Shock resistance 15 gn for 11 ms conforming to IEC/EN 60068-2-27
Pollution degree 1 HP to 25 HP @ 200/240 V, 1 HP to 5 HP @ 380/480 V: Pollution degree 2 per IEC/EN 61800-5-1, 30
HP to 40 HP @ 200/240 V, 30 HP to 100 HP @ 380/480 V: Pollution degree 3 per IEC/EN 61800-5-1
Degree of protection: ATV212 H range
ATV212 W range
IP20, Conformal coating per IEC 60721-3-3 classes 3C2 and 3S2, Type 1 with optional conduit kit
IP54/Type 12, Conformal coating per IEC 60721-3-3 classes 3C2 and 3S2
Electrical Specifications
Input voltage and HP range ATV212 W
is available in 380/480 range only
200 – 15% to 240 +10%, Three phase input, Three phase output, 1 HP to 40 HP
380 – 15% to 480 +10%, Three phase input, Three phase output, 1 HP to 100 HP
Input frequency 50 Hz -5% to 60 Hz +5%
Galvanic isolation Galvanic isolation between power and control (inputs, outputs and power supplies)
Drive input power section Six pulse bridge rectier
Drive output power section IGBT inverter with pulse width modulated output
Power factor Above 99%
Efciency Above 98% at full load
Switching frequency Selectable from 6 to 16 kHz, 12 kHz nominal rating for 1 HP to 20 HP @ 200/240 V, 380/480 V
Selectable: 6 to 16 kHz, 8kHz nominal rating for 30 HP to 40 HP @ 200/240 V, 30 HP to
100 HP @ 380/480 V
Acceleration and deceleration ramps 0.1 to 3200 seconds in 0.1 seconds increments
Frequency output range 0.5 to 200 hertz
Skip frequencies Three adjustable skip frequency bands
Speed range 1 to 10
Integrated motor protection Class 10 electronic overload protection
Asynchronous motor control proles Sensorless ux vector, 2 point volts/hertz, quadratic volts/hertz, energy savings mode: a optimization
motor algorithm that automatically optimizes voltage based on load
Transient over current 110% nominal for 60 seconds, 180% for 2 seconds
Embedded functions Over 50 functions dedicated to pump and fan applications
User interface On board: 5 LED indicators for various functions, 4 digit, 7 segment LED display with 7 button keypad
for: Run, Stop/Reset, Local/remote, Speed up, speed down, Mode selection and Enter. Quick start
menu, fault history, I/O mapping, last-used menus, status monitoring and self diagnostics. Fault
messages and status such as: power on time, elapsed time, motor run time, line voltage, motor
current, ready to run, running, motor speed, etc.
Embedded communication Embedded RJ45 port for remote keypad connection, Multi-loader, PC software, or Bluetooth dongle
for So Mobile smart phone connection. Embedded 4 screw removable terminal for daisy chain
connection for: Modbus, BACnet, Metesys N2, or Apogee P1 communication networks.
Harmonic abatement Embedded reduced harmonic technology provides <35% THDI at VFD input terminals,
which is equivalent to a 3% line reactor or DC choke. See technical paper 8800DB0702
for more information.
EMC compliance: ATV212 H and W N4 range:
ATV212 W N4C range:
ATV212H M3X range:
Integrated Class 2 EMC lter for radiated and conducted emissions, IEC 61800-3, category C2 and C3
Integrated Class 2 EMC lter for radiated and conducted emissions, IEC 61800-3, category C1
No integrated EMC lter (use optional lters to reduce emission levels)
Compliance UL 508C, RoHS, IEC 61800-5-1, IEC/EN61000-3-12 THDI harmonic standard
Certications UL File E116875, CSA 2278406, UL 508C, Plenum rated per UL508C for UL1995 installations,
C-Tick, NOM 117, CE marked